The Short Answer
Ask whoever installed or maintains the equipment one question in writing: can this controller be reached directly from the internet? If the answer is yes, or nobody knows, treat it as exposed and have the direct access removed. The steps below are for the owner or manager of a shop, cold store, kitchen, laboratory or building who wants to check their own equipment. They follow the guidance issued by France's CERT-FR, EU bodies and US agencies after the refrigeration attacks of October and November 2026.
Check only equipment you own or operate. If you find a problem with someone else's system, tell them or your national cyber agency.
Step 1: List What You Have
You cannot check what you do not know about. For each site, write down:
- Every system that controls something physical: refrigeration, heating and cooling, ventilation, lighting, doors, alarms, energy meters.
- The make and model of the controller or system manager, read from the label on the unit.
- The software or firmware version, usually shown on the unit's own screen or in its settings menu.
- Who installed it, who maintains it, and whether they connect remotely.
- How it connects: through your office network, through its own router, or through a mobile data modem with a SIM card.
Look in the plant room for small boxes with antennas. A US CISA alert of July 30, 2026, cited by Censys, warned that cellular modems on control equipment may be undocumented and missed in routine checks.
Step 2: Ask the Installer or Maintainer
| Question | The answer you want |
|---|---|
| Can the controller be reached directly from the internet? | No |
| How do your technicians connect remotely? | Through a VPN or a secured service, with a login for each person |
| Is there a public address or a forwarded port for this equipment? | No |
| Is the default password still in use on any account? | No, and here is when it was changed |
| What firmware version is installed, and is it the latest? | A version number and a date |
| Does the manufacturer still issue updates for this model? | Yes. If no, ask for a replacement plan |
| Who gets the alarm if the temperature leaves its range, and does that alarm work if the controller itself is tampered with? | A named person, and an independent alarm |
Ask for the answers in writing. CERT-FR also advises checking the terms of your insurance contract before cutting any data feed to your refrigeration contractor, since some policies require remote monitoring.
Step 3: Check Your Own Network Settings
If you manage the router or firewall at the site, or your IT provider does, look at its settings from the inside:
- Port forwarding: open the router's administration page and find the port forwarding or virtual server list. Any entry that points at the controller's address means it is being offered to the internet.
- Exposed host settings: check that the controller is not set as an exposed host, sometimes labelled DMZ.
- Automatic port opening: turn off the feature that lets devices open ports by themselves, usually labelled UPnP.
- Public address: ask your internet or mobile provider whether the line or SIM has a fixed public address. Control equipment should not sit on one.
- Separation: control equipment should be on its own network segment, apart from tills, office PCs and guest wifi.
If these terms are unfamiliar, hand this list to your IT provider. Do not use outside scanning tools against addresses you are not sure are yours.
Step 4: Remove Direct Access and Restore It Safely
CERT-FR's order of work for equipment that has not been tampered with:
- Remove internet exposure for the affected units and for any unit on a public address.
- Review the whole configuration, including defrost schedules, and compare it with what it should be.
- Restore remote access only through a secured VPN or protected network. Allowing only the contractor's addresses through a firewall is acceptable as an emergency measure, not as a lasting fix.
- Apply the manufacturer's recommended settings and updates.
Greece's National Cybersecurity Authority adds multi-factor authentication for remote access.
Step 5: Update, and Change Default Passwords
| Product family | What the manufacturer has said |
|---|---|
| Danfoss AK-SM 800A | Upgrade to firmware R4.3.1 or later. Do not expose the management interface to the internet |
| Danfoss AK-SM 800 and AK-SC 355 | Legacy products that no longer receive software or security updates. Danfoss advises moving to current systems |
| Copeland XWEB300D PRO and XWEB500D PRO | Firmware version 1.13, issued February 2026 |
| Dixell XWEB | A guide to secure use of XWEB supervisors, referenced in the CERT-FR alert |
Change every default password, give each technician their own login, and remove accounts for people who have left. For Danfoss units, CERT-FR recommends setting the security level to its strict mode. If a model can no longer be updated, keeping it reachable from the internet carries, in CERT-FR's words, a very high probability of compromise. Plan its replacement.
Step 6: Watch the Advisories
- Your manufacturer's security advisory page.
- Your national cyber agency. In France, CERT-FR alert CERTFR-2026-ALE-012.
- ENISA's collection of national advisories on the retail incidents, referenced in the EU joint statement of November 4, 2026.
- In the US, the joint advisory from the FBI, CISA and three other agencies of November 5, 2026.
If Settings Have Already Been Changed
- Deal with safety first: stock, fire risk, and anything temperature-sensitive.
- Disconnect the unit from the internet.
- Restart it, or restore factory settings if a restart is not enough, then reconfigure before returning it to service. CERT-FR warns that a factory reset alone leaves an unpatched device open to being taken over again.
- Keep a record of what you found and when.
- Report it.
Who to Report To
- Your installer and the manufacturer, so other customers can be warned.
- The police, as with any crime.
- Your national cyber agency or response team, such as CERT-FR in France or the NCSC in the UK. Organisations covered by NIS2 must report significant incidents to their national team. See the NIS2 enforcement tracker.
- Your insurer.
For background on why this equipment is exposed so often, see operational technology security and the counts in exposed control systems by country.
Sources
CERT-FR alert CERTFR-2026-ALE-012, as updated October 16, 2026; the EU joint statement of November 4, 2026; BleepingComputer on the US joint advisory; Cooling Post on manufacturer updates; Facilities Dive on the Danfoss statement; To Vima on the Greek guidance; and Censys. This is general guidance, not a substitute for advice from your manufacturer or national agency. Read November 13, 2026.